Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM04173
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/25/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide justification for the stated maximum occupancy of 300 people in the Sanctuary (e.g. Load Card or C of O limitation) or comply with the ventilation rates shown in Table 403.3, IMC 2000. 2. Show size, route, and termination of condensate drain from AC-1. |
| 08/26/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/10/2003 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 10/10/2003 | SREEVES1 | FIRE | REVIEW | Needs Review | |
| 10/10/2003 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/10/2003 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 10/10/2003 | SREEVES1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |