Permit Number: T03CM04155
Parcel: 12002041A

Address:
727 W AJO WY

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04155
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied Show a riser diagram of the CW-HW piping. Include the sizes of the main CW supply and the existing piping that is serving the new piping.
11/14/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The equipment schedules indicate that exhaust fans EF-4 and EF-1 are to be ducted through the wall and terminate with wall caps but the mechanical plan shows both fans being ducted through the roof. Please clarify.
12/01/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied . T03CM04155 .. 727 W AJO WAY,#175 .. DGL .. 12/02/03 .
S1. SEE PRIOR COMMENT #S1. PROVIDE UPDATED OFFICIAL ADDRESS SLIP, SHOWING DINING ADDITION OF 810 SF TO EXISTING PIZZARIA 1810 SF UNDER SPECIAL CONDITIONS.
S2. SEE PRIOR COMMENT #S2.
1. ADDRESS SITE ACCESSIBILITY PER PRIOR ITEM #S2.3. PROVIDE NOTE ON DRAWING #T1.
2. PROPERLY LOCATE REAR GRAB BAR (A3) END 6" FROM ADJACENT WALL, WITH 12" POINT OF BAR AT CENTERLINE OF WATER CLOSET, PER ANSI A117.1-1998 ed FIG #604.5.2.
S3. STRUCTURAL ENGINEER NEEDS TO SEAL DRAWING/S IN SET RELATED TO HIS CALCULATIONS.
If you have questions, please call Douglas Laakso, Structural Plans Examiner, (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
12/02/2003 ANGIE SHOFFSTALL REJECT SHELF Completed