Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM04155
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation for new and rearranged areas. Reference Section 401, IMC 2000. 2. Provide structural support details, duct construction information, and air balancing information for relocated hoods. Reference Sections 506, 507, and 508, IMC 2000. 3. Provide manufacturer's equipment data along with mechanical and electrical operating information for the new exhaust fans. Reference Section 301.6, IMC 2000. |
| 08/22/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. Include existing fixtures and directly connected kitchen equipment when determining total demand. |
| 08/22/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/26/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/29/2003 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Denied | S1. PROVIDE OFFICIAL ADDRESS SLIP TO SHOW ADDITION TO THIS TENANT SPACE FROM PIMA COUNTY ADDRESSING. .................................... .................. ..... S2. CLARIFY ACCESSIBILITY, PER IBC CHAPTERS 11 & 34: ...... 1. DINING , AT EXISTING COLUMN , DIMENSION TO SHOW ACCESSIBILITY. .................................................... ...... 2. EXTERIOR DOOR ADJACENT TO MEN'S TOILET ROOM APPEARS CLEARANCE AT TOILET ROOM PARTITION IS NOT ENOUGH , REVISION MAY REQUIRE TOILET ROOM/S TO BE REVISED AS WELL. ............... ...... 3. ADDRESS SITE ACCESSIBILITY. ........................... ...... 4. CLARIFY HOW COMPLIANCE IS MET, NOTE ON DRAWINGS .................................................................... ...... 5. EXPLAIN ACCOMMODATIONS AT COUNTERS. ....... ...... 6. PROPERLY LOCATE REAR GRAB BAR (A3). ............ 3. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS FOR NEW/ RELOCATED EQUIPMENT SUPPORTED BY ROOF FRAMING. DIMENSIONALLY LOCATE ROOF MOUNTED EQUIPMENT , HOODS, AC ,etc. |
| 09/04/2003 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. Sheet E1 1. Note 5, please change NEC Table 250-118 to 250-122, since the intent is to size the EGC. Believe this was a "typo", as there is no NEC Table 250-118. 2. Panel Schedules show rating of "1 K AIC". Certainly another "typo." 3. Circuit A-27 shows load as Right Turn Signal. Please verify. Sheet E2 1. Hood lights on B-5, but on Panel Schedule this Circuit is listed as a spare with no load. 2. Keynotes 7 & 8 on the Lighting Demolition Plan appear to belong on the actual Lighting Plan. 3. Provide Panel, Circuit, and electrical load for Fixtures D, over tables in northeast corner. 4. Provide Panel, Circuit, and electrical load for Fixtures C, A, and relocated fixtures in southeast corner of restaurant. Sheet E3 1. Receptacles on B-29, but on Panel Schedule this Circuit is listed as having no load. 2. Receptacles on B-17,19, but on Panel Schedule B-19 is listed as a spare with no load. 3. In Room 104 Circuits A-26,28 come from "TC" inside of a square symbol, not on List of Electrical Symbols. Please verify that Vista Cooler and Hot Shot, existing on Panel Schedule, are indeed to be powered in this fashion. 4. In Room 104 Circuits B-22,24 come from "TC" inside of a square symbol, not on List of Electrical Symbols. Please verify that Bread Stick, existing on Panel Schedule, are indeed to be powered in this fashion. 5. In Room 104 Circuit B-26 comes from "TC" inside of a square symbol, not on List of Electrical Symbols. This Circuit is used for the new Track Lighting. Please verify powering in this fashion. 6. In Room 104 Circuit B-28 comes from "TC" inside of a square symbol, not on List of Electrical Symbols. This circuit is listed as a spare on the Panel Schedule. Please resolve. 7. Dishwasher on A-11. Provide disconnect per NEC 422-31, or verify that CB can be locked in open position. 8. Special outlet on B-35 on Power Plan. This circuit is listed as a spare with no load on the Panel Schedule. 9. Receptacles on B-13,15 on Power Plan Room 109. On Panel Schedule B-13 is part of 2-pole CB B-11,13, and B-15 Drive through. Please resolve. 10. Circuit 19,21, existing oven, has a 60A CB on Panel Schedule. Other 2 ovens on this Panel have same KVA, but are on 20A CB, more appropriate for their VA rating. Please correct as necessary. |
| 09/08/2003 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/11/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |