Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM04153
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/22/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include all existing fixtures in the fixture unit calculation, including hose bibbs. 2. Provide drawing and calculations of gas piping being modified. 3. Show size, route, and termination of condensate piping being modified. |
| 08/22/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ON APPLICATION. |
| 08/22/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/22/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the ventilation in the area comforms to the requirements of Section 403, IMC 2000. |
| 08/25/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/25/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | denied 8/25/03 1. Work in patient care areas per 517-13. 2. Keynote 4 per NEC 800-40 (b). |
| 09/30/2003 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 09/30/2003 | DROBEY1 | ZONING | REVIEW | Needs Review |