Permit Number: T03CM04153
Parcel: 10504028J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM04153
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2003 JIM EGAN FIRE REVIEW Approved
08/22/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include all existing fixtures in the fixture unit calculation, including hose bibbs.
2. Provide drawing and calculations of gas piping being modified.
3. Show size, route, and termination of condensate piping being modified.
08/22/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.
08/22/2003 ROBERT SHERRY WATER REVIEW Approved
08/22/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the ventilation in the area comforms to the requirements of Section 403, IMC 2000.
08/25/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/25/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied denied 8/25/03
1. Work in patient care areas per 517-13.
2. Keynote 4 per NEC 800-40 (b).
09/30/2003 DROBEY1 WWM REVIEW Needs Review
09/30/2003 DROBEY1 ZONING REVIEW Needs Review