Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM04112
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2003 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 09/08/2003 | SREEVES1 | WATER | REVIEW | Needs Review | |
| 09/08/2003 | SREEVES1 | FIRE | REVIEW | Needs Review | |
| 09/08/2003 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 09/08/2003 | SREEVES1 | ENGINEERING | REVIEW | Needs Review | |
| 09/08/2003 | WILDAN | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS: Sheet A0.6 1. Provide missing Keynote #35. Reference IBC Section 106.1.1. STRUCTURAL COMMENTS: Sheet A0.8 1. Provide the manufacturer's specifications and calculations for the Light Pole Foundations. Reference IBC Section 106.1.1. PLUMBING COMMENTS: The plumbing portion was not a part of this review. MECHANICAL COMMENTS: The mechanical portion was not a part of this review. ELECTRICAL COMMENTS: 1. Provide the lighting manufacturer's catalog cut sheets of the light heads to verify compliance with the City of Tucson Lighting Ordinance ENERGY CODE COMMENTS: The energy code portion was not a part of this review. ACCESSIBILITY COMMENTS: The accessibility portion was not a part of this review. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |