Permit Number: T03CM04100
Parcel: 116277250

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM04100
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2003 JIM EGAN FIRE REVIEW Approved
08/22/2003 ROBERT SHERRY WATER REVIEW Passed
08/22/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/22/2003 RSCHULE1 WWM REVIEW Passed
08/25/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Provide a soils report for the retaining walls, control building, and storage tank areas. Reference section 1802.6 IBC
2. Site drainage flows over retaining wall slopes. How is slope stability to be maintained?
3. Indicate soils type to be used for backfill on lower retaining wall that would be conducive for the proposed drainage system.
4. The control building, 5,000-gallon storage tank, and power transformer are in close proximity to the upper level retaining wall. Retaining wall calculations do not address these loads. Please clarify.
5. Structural engineer to seal plans for proposed retaining walls.
6. Special Inspection required for site preparation, masonry, concrete, welding, and foundation excavation. Indicate on plans
7. Lower wall is being partially constructed on the adjacent property. Revise plans
08/28/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
09/02/2003 CRAIG GROSS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/04/2003 LISA LESNY OUT TO CUSTOMER Completed