Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM04073
Parcel: Unknown

Address:
4380 E 22ND ST

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM04073
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2003 JIM EGAN FIRE REVIEW Approved
09/12/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Needs Review
09/15/2003 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
09/15/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a schedule of water and waste fixture units for all plumbing fixtures (including hose reels and kitchen equipment requiring water or drain connections) using the values shown in Tables 6-3 and 7-3, UPC 1994. Include the total number of each fixture being installed. Reference Section 302.3, Uniform Administrative Code 1997.
2. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
3. Provide calculations and sufficient information on the drawing to show that the new water supply piping is sized in accordance with Section 610.4, UPC 1994 and that the additional fixtures will not overload the existing piping.
4. Provide information to show that the hub drain (Detail 2/P1) complies with Section 410.1, UPC 1994 and indicate the locations for its use.
5. Modify trap arm length of FS-1 at the Bakery Bar to conform to Table 10-1, UPC 1994 with AZ State amendments.
6. Provide a vent for floor sink FS-2 at the Bakery Bar. Reference Section 901.0, UPC 1994.
7. Note 21 on sheet P1 calls for grease drains from the new exhaust fans to be piped to floor sinks. Provide information to show that this will not violate the requirements of Sections 714.1 and 1008.1, UPC 1994.
8. Provide the listing for the gas appliance connectors. The use of gas flex hose does not appear to be justified for this application. Reference Section 1212.0, UPC 1994.
09/15/2003 TACHONG1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2003 TAMI ACHONG OUT TO CUSTOMER Completed