Permit Number: T03CM04068
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM04068
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Approved
12/04/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
12/09/2003 Loren Makus ENGINEERING REVIEW Approved
12/11/2003 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T03CM04068 .. 7290 E TANQUE VERDE RD .. 12/12/03 .. .. PRIOR COMMENTS DATED 9/5/03 .. DGL.
S1. SEE PRIOR COMMENT #1. SHOW COMPLIANCE WITH ANSI A117.1-1998ed. PROVIDE 60" x 60" LANDING AT TOP OF RAMP, AT E/19, IN LINE WITH TRAEL ON RAMP, DUE TO TURN IN SIDEWALK. PROVIDE CURB RAMP DETAILS, ON DRAWINGS, (REFERENCE TO SOME STANDARD IS NOT ACCEPTABLE), SHOWING COMPLIANCE WITH IBC SEC 11 AND ANSI A117.1-98ed SEC 406.
S2. SEE PRIOR COMMENT #3. IF STATE OF ARIZONA IS PERMITTING TOILET ROOMS, PLEASE NOTE THIS ON DRAWING #5, LAYOUT AND CONSTRUCTION NOTE #5.
Spoke with Jason at The Acacia Group regarding these comments.
Questions ? Please call Douglas Laakso, Structural Plans Examiner, at (520) 791-5550 x 1111.
.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2003 DELMA ROBEY OUT TO CUSTOMER Completed