Permit Number: T03CM04068
Parcel: Unknown

Review Status: Completed

Review Details: SITE

Permit Number - T03CM04068
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2003 JIM EGAN FIRE REVIEW Approved
09/22/2003 LOREN MAKUS SANITATION REVIEW Passed
09/22/2003 LOREN MAKUS ENGINEERING REVIEW Denied DATE: September 22, 2003
TO: Mr. Walt Rogers, The Acacia Group
SUBJECT: Udall Park Improvements Site and Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T03CM04068 and T03BU02138

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department, Engineering Division. The Site Plan and Grading Plan were not approved at this time. Please address the following comments.

Site Plan and Grading Plan Comments:
1) Provide a site plan with lot dimensions and bearings (including basis of bearing), sight visibility triangles and points of egress and ingress. (Per Development Standard 2-02.2.1.A)
2) Revise the sheet index on page 13 to be consistent with the page numbers of the plan set. Revise the site plan so that all of the type is 12 point or larger.
3) Clarify the extent of the disturbed area. Give the area in acres or square feet.
SWPPP Comments:
4) Show how the undisturbed protected areas will be marked to prevent inadvertent disturbance.
5) Clarify the extent of the disturbed area. Give the area in acres or square feet. Ensure that this number matches the information on the Site Plan

Revise the site plan to address all of these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
10/02/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See zoning review comments
10/02/2003 PETER MCLAUGHLIN ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Walt Rogers
3861 N. First Avenue
Tucson, AZ 85719
(520) 407-9071

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T03CM04068
Morris K. Udall Park Improvements
7290 E. Tanque Verde Road
Site Plan Review (1st review)

TRANSMITTAL: October 2, 2003


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan is being reviewed as a less than 25 % expansion. Please provide a copy of the last approved site plan with the next submittal.

2. Provide a site plan with all required components and specifications listed in DS 2-02, including parking calculation (see comment 4), lot dimensions and bearings, zoning and adjacent zoning (see comment 3), sight visibility triangles, egress/ ingress points.
DS 2-02

3. Please provide the current zoning for the site and adjacent properties on the plan. The zoning on the entire site is SR. Adjacent zoning to the south of the park is SR, adjacent zoning to the east is R-3 and R-1, zoning to the west is C-1, RX-2, SR and R-2
DS 2-02.2.1.A.28

4. Add vehicle and bicycle parking calculations to the site plan, showing the number of spaces required and provided with the proposed improvements. Include calculations for handicap parking required/provided. Vehicle parking is based on the number of tennis courts (2 parking spaces required per court) and number of athletic fields (15 parking spaces required per soccer field). Bicycle parking is required at a rate of 15% of the vehicle parking provided.
DS 2-02.2.1.A.8
DS 2-02.2.2.A.4

5. Show the location of and provide a fully dimensioned layout for any new bicycle parking proposed. Also, indicate the specific type of rack and the number of bicycles it supports.
DS 2-02.2.1.A.9
DS 2-09.6.0

6. Add a note stating that no loading zones are required or proposed.
DS 2-02.2.2.A.5

7. Add a general note stating that no new buildings are proposed.
DS 2-02.2.1.A.6

8. Add the development designator to the general notes. The development designator for the recreation use in the SR zone is "6".
LUC 2.2.4.2.E.2

9. Provide a general note stating that the project is in compliance with the restrictions detailed in 3.5.13.2 and 3.5.13.3, which limit the hours of operation and the location and direction of outdoor lighting respectively.
LUC 2.2.4.2.E.2

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
10/18/2003 JOE LINVILLE NPPO REVIEW Approved
10/18/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. LUC 3.7.4.3.B
Revise the landscape plan and grading plans to include or identify water harvesting areas.

2) Revise the plans for the project area to comply with LUC 3.7.2.7 which requires that "All disturbed, grubbed, graded, or bladed areas not otherwise improved shall be landscaped, reseeded, or treated with an inorganic or organic ground cover to help reduce dust pollution.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2003 TAMI ACHONG OUT TO CUSTOMER Completed
10/20/2003 ANGIE SHOFFSTALL REJECT SHELF Completed