Permit Number: T03CM04068
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM04068
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Passed
08/28/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide specifications for backflow preventer noted on Sheet 16
2. Provide shut-off valve for water supply to modular restroom. Reference Section 605.0, UPC 1994.
3. Label size of water supply pipe feeding modular restroom (Sheet 16).
08/28/2003 ROBERT SHERRY WATER REVIEW Approved
09/04/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE DETAILS ON DRAWINGS FOR ACCESSIBILITY AT PARKING, ACCESS RAMPS, LANDINGS, WITH SLOPES, ELEVATIONS, AND LOCATIONS, REF. DRAWING #14 AND #15, PER IBC SEC #11. ........................................... ...... 2. PROVIDE COPY OF STRUCTURAL CALCULATIONS FOR FOUNDATIONS. .................................................. .......... 3. PROVIDE TWO SETS OF APPROVED SHOP DRAWINGS FOR : 1. RESTROOMS ...................................................... 2. CHAINLINK FENCING .......................................... 4. PROVIDE INSPECTION PROGRAM PER 1997 UAC SEC 302.5. ............................................................................. 5. SPECIAL INSPECTION REQUIRED FOR : . 1. FOUNDATION EXCAVATIONS . 2. CONCRETE . 3. BOLTS IN CONCRETE . 4. REINFORCING.
09/16/2003 JIM EGAN FIRE REVIEW Approved
09/16/2003 LOREN MAKUS ENGINEERING REVIEW Denied DATE: September 22, 2003
TO: Mr. Walt Rogers, The Acacia Group
SUBJECT: Udall Park Improvements Site and Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T03CM04068 and T03BU02138

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department, Engineering Division. The Site Plan and Grading Plan were not approved at this time. Please address the following comments.

Site Plan and Grading Plan Comments:
1) Provide a site plan with lot dimensions and bearings (including basis of bearing), sight visibility triangles and points of egress and ingress. (Per Development Standard 2-02.2.1.A)
2) Revise the sheet index on page 13 to be consistent with the page numbers of the plan set. Revise the site plan so that all of the type is 12 point or larger.
3) Clarify the extent of the disturbed area. Give the area in acres or square feet.
SWPPP Comments:
4) Show how the undisturbed protected areas will be marked to prevent inadvertent disturbance.
5) Clarify the extent of the disturbed area. Give the area in acres or square feet. Ensure that this number matches the information on the Site Plan

Revise the site plan to address all of these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed.

Loren Makus
Senior Engineering Associate
Engineering Division
Development Services
09/22/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Approved
09/23/2003 GERRY KOZIOL WWM REVIEW Approved
10/02/2003 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2003 TAMI ACHONG OUT TO CUSTOMER Completed
10/20/2003 ANGIE SHOFFSTALL REJECT SHELF Completed