Permit Number: T03CM04044
Parcel: 118060600

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM04044
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2003 MELISSA POULIN WWM REVIEW Approved
09/24/2003 Martin Haeberle BUILDING-RESIDENTIAL REVIEW Denied 1. Provide energy calculations that indicate compliance with the 1998 International Energy Conservation Code.
2. Plans are required to reflect criteria of the energy calculations. Revise plans.
3. Provide cross-sections of walls/ columns, and wall openings showing reinforcing steel placement per figure R606.10 IRC.
4. Indicate ledger bolt placement per figure R606.10 IRC
5. Plans to have wood species and grades on plans for all structural members
6. Specify all TJI's to be 150's or specify type for each roof area.
7. Show on plan location of garage dwelling separation and how protection of openings complies with section R309 IRC.
8. Provide header sizes for interior bearing walls.
9. Provide steel grades for proposed steel lintels.
10. How is shear transfer of steel lintels accomplished? Provide detail.
11. Wood lintels are not allowed to support masonry. Revise plans
12. Provide developed length of water line and meter size.
13. Two 20 small appliance circuits required in kitchen. Reference section E3801.3 IRC. Revise plans
14. All receptacles serving countertops in kitchens shall be GFI's. Reference section E3802.6 IRC
15. Provide an outlet at the front and back of the house. Reference section E3802.3 IRC

Final Status

Task End Date Reviewer's Name Type of Review Description
09/24/2003 LISA LESNY OUT TO CUSTOMER Completed
09/24/2003 ANGIE SHOFFSTALL REJECT SHELF Completed