Permit Number: T03CM04028
Parcel: 120086690

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM04028
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2003 EROSE1 WWM REVIEW Needs Review
08/21/2003 DOUG WILLIAMS ENGINEERING REVIEW Needs Review
08/21/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

2. The vacuum canopy and drying canopy is noted by others. However, the electrical plans have lighting and other details shown for those canopies. The mechanical plans do not show anything. Please coordinate and clarify that work as either being wholly a deferred design submittal or separate permit. Reference IBC Section 106.


ARCHITECTURAL COMMENTS:

Sheets A2.1 and A7.1

1. Detail-2 does not satisfy the 2000 IBC requirement for a primary and secondary roof drainage system when storm water cannot drain freely over the eaves. The secondary roof drainage system shall be designed for twice the design rainfall. Please review and clarify. Reference IBC Section 1503.4, IPC Section 1107, and IBC Section 102.4.

Sheets A6.1

1. Gypsum board is noted for installation over the automatic car washing line. Please clarify specific manufacturer's material for the proposed high humidity ceiling installation. Reference IBC Section 2509.


STRUCTURAL COMMENTS:

Sheet S1.1

1. The Specification for Masonry Structures is ACI 530.1. Please correct reference notation.

2. The roof trusses are noted for design by a truss manufacturer. Please complete enclosed deferred design submittal request letter to the Building Official. Reference IBC Sections 106.3.3 and 106.3.4.

3. The City of Tucson Special Inspection and Testing Agreement is enclosed for your use. Please complete and return with your resubmittal.

Sheet S1.2

1. Detail-2 slope should be a 30o angle from the horizontal. Reference IBC Section 1805.2.2.


PLUMBING COMMENTS:

Sheet P2.1

1. Interior and exterior waste drainage piping shall slope at 2%. Reference UPC Section 708/718.

2. Note code compliance with 2000 IBC, 1998 IECC as adopted by the City of Tucson, and the 1994 UPC with State of Arizona amendments. Reference IBC Section 106.1.1.


MECHANICAL COMMENTS:

Sheet M2.1

1. Note code compliance with 2000 IBC, 1998 IECC, and the 2000 IMC as adopted by the City of Tucson. Reference IBC Section 106.1.1.


ELECTRICAL COMMENTS:

Sheet E1.1

1. The structures associated with the electrical work are noted by others and are not detailed on the structural plans. Please coordinate with architect for building work that may be under a separate permit application and not shown for this permit application. See general comment #2 above. Reference IBC Section 106.

Sheet E4.1

1. Code compliance shall be noted to the 2000 IBC, 1998 IECC, and 1999 NEC as adopted by the City of Tucson. Reference IBC Section 106.1.1.


ENERGY CODE COMMENTS:

Sheet A3.1

1. Glazing shall be noted to have SHGC £ 0.4 and U-value £ 0.7. Reference IECC Table 702.2 (12).


ACCESSIBILITY COMMENTS:

Sheets A1.2 and A4.1

1. Show that ADA toilet room has required 5-foot turning circle. Reference IBC Section 1108 and ANSI 117.1.
08/21/2003 ELAINE ROSE ZONING REVIEW Needs Review
08/21/2003 EROSE1 WATER REVIEW Needs Review
08/21/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2003 ELAINE ROSE OUT TO CUSTOMER Completed