Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The water calculations and fixture unit schedule on the drawing indicate that the existing 1" water service is undersized. Reference Section 610.1, UPC 1994.
09/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM03983

9/3/03 DENIED

1- "Per NEC 680-41 (b) (1) or (2), demonstrate compliance." This comment was made on the first review. General Note 3 does not describe full compliance with this Code section. Please review the section and rephrase the note.
2- Plan view indicates disconnect switch for WH, but panel schedule indicates receptacle. Please clarify.