Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03983
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The water calculations and fixture unit schedule on the drawing indicate that the existing 1" water service is undersized. Reference Section 610.1, UPC 1994. |
| 09/03/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM03983 9/3/03 DENIED 1- "Per NEC 680-41 (b) (1) or (2), demonstrate compliance." This comment was made on the first review. General Note 3 does not describe full compliance with this Code section. Please review the section and rephrase the note. 2- Plan view indicates disconnect switch for WH, but panel schedule indicates receptacle. Please clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/08/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |