Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03983
Parcel: 121080240

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM03983
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide reduced pressure backflow preventers on hot and cold water supplies to the foot spa.
2.Provide detail of water heater installation. Detail to include piping, valves, expansion tank, and T&P relief.
3. Provide water pressure calculations to show how the water pipes were sized.
4. Provide water isometric with all pipe sizes shown.
5. Clarify how the air gap fitting is being applied. the air gap fitting must be above the flood rim of the sink. If the drain from the air gap fitting is to be connected to the sink drain, show it connecting upstream of the trap (on the sink tailpiece).
6.The architect's seal must be legible.
08/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM03983

8/12/03 DENIED:
1- Provide emergency shutoff or control switch per NEC 680-38. Plans difficult to read. No able to tell if panelboard feeding this equipment is within sight of it.
2- Per NEC 680-41 (a), locate the receptacle 5-10 feet from the inside wall of the spa.
3- Per NEC 680-41 (a) (1), Existing receptacles are too close to the spa.
4- Per NEC 680-41 (a) (2) such receptacles shall be GFCI protected if within 10' of the spa.
5- Per NEC 680-41 (b) (1) or (2), demonstrate compliance.
6- Per NEC 680-41 (c), demonstrate that there are no wall switches within 5' of the spa.
7- Specify bonding per NEC 680-41 (d) & (e).
8- Specify grounding per NEC 680-41 (g) (2).

Final Status

Task End Date Reviewer's Name Type of Review Description
09/03/2003 TAMI ACHONG OUT TO CUSTOMER Completed