Permit Number: T03CM03933
Parcel: 12613018A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03933
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2003 JIM EGAN FIRE REVIEW Approved
08/08/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
08/08/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
08/08/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved 8/8/03

1. Instantaneous water heater is 120V on Sheet MP.1 and 240V on E.1. Please clarify.
2. Please clarify amperage on heat pumps. HP-1 5 ton, HP-2 4 ton. There is only 3 amps difference between the two on the electrical load calculation.
3. Show protection for conductors feeding New Panel A.
4. Show method of connection of conductors from disconnect to Service A to new disconnect for HP-1.
5. Specify conduit size and type, and conductor size and type, for all such new equipment of Line Diagrams.
6. Specify protection for conductors from service disconnect for Service A to HP-1 disconnect.
7. Provide available fault current from TEP on plans, and fault calculations as necessary to demonstrate that rating of panels is sufficient.
8. Load calculation for Service B shall include that for existing tenant.
9. Circuits B-3 and B-5 each contain 4 receptacles. Correct to 180 VA per receptacle.
08/08/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/13/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/13/2003 ROBERT SHERRY WATER REVIEW Approved
08/13/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/14/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/14/2003 TAMI ACHONG OUT TO CUSTOMER Completed