Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03928
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/08/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/08/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/08/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/08/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Calculate minimum outside air requirements using Chapter 4, IMC 2000, not ASHRAE 62 or UBC 1200. 2. Coordinate outside air flow rates shown on Outside Air Compliance Schedule with equipment schedule. 3. Provide outside air for corridor and utility room (103). |
| 08/13/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/13/2003 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 08/13/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | |
| 08/13/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |