Permit Number: T03CM03916
Parcel: 123172560

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM03916
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 2.0
1. The dwelling unit separation references shown as details 2 and 3 on this sheet do not appear to be continuous. Please clarify.


STRUCTURAL COMMENTS
Sheet 4.0
1. Specify the footing type at the new to existing foundation condition.


PLUMBING COMMENTS - The plumbing portion has been reviewed and approved.




MECHANICAL COMMENTS
Sheet 7.0
1. Please revise notes 1,5,8,9,and 10 to indicate the 1994 UPC as amended in lieu of IRC Chapter 17. All of IRC Chapter 17 has been deleted by local amendments and uses the State Plumbing Code in place of IRC Chapter 17

ELECTRICAL COMMENTS
Sheet 8.0
1. Please complete the circuit information for the kitchen and bedroom 5.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
08/25/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2003 ELAINE ROSE OUT TO CUSTOMER Completed