Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM03916
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet 2.0 1. The dwelling unit separation references shown as details 2 and 3 on this sheet do not appear to be continuous. Please clarify. STRUCTURAL COMMENTS Sheet 4.0 1. Specify the footing type at the new to existing foundation condition. PLUMBING COMMENTS - The plumbing portion has been reviewed and approved. MECHANICAL COMMENTS Sheet 7.0 1. Please revise notes 1,5,8,9,and 10 to indicate the 1994 UPC as amended in lieu of IRC Chapter 17. All of IRC Chapter 17 has been deleted by local amendments and uses the State Plumbing Code in place of IRC Chapter 17 ELECTRICAL COMMENTS Sheet 8.0 1. Please complete the circuit information for the kitchen and bedroom 5. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
| 08/25/2003 | EROSE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/25/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |