Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM03897
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/07/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Roof overhang exceeds allowable encroachment of property line by 6" per section 704.2 IBC. Revise plan 2. Revise allowable area calculations to include Recreation Room. Reference section 503.1.3 IBC 3. Ramada to be classified an A-3. Reference section 303 & 312 IBC. Revise plans and calculations. 4. Proposed ramada revises occupant load for pool area. Provide occupant load calculations and means of egress. Note: Appears one exit does not open in direction of travel. Reference Table 1003.2.2.2 |
08/11/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
08/11/2003 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
08/11/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
08/11/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/11/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |