Review Details: COMMERCIAL NEW

Permit Number - T03CM03897
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Roof overhang exceeds allowable encroachment of property line by 6" per section 704.2 IBC. Revise plan
2. Revise allowable area calculations to include Recreation Room. Reference section 503.1.3 IBC
3. Ramada to be classified an A-3. Reference section 303 & 312 IBC. Revise plans and calculations.
4. Proposed ramada revises occupant load for pool area. Provide occupant load calculations and means of egress. Note: Appears one exit does not open in direction of travel. Reference Table 1003.2.2.2
08/11/2003 JIM TATE ENGINEERING REVIEW Approved
08/11/2003 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Passed
08/11/2003 JIM EGAN FIRE REVIEW Approved
08/11/2003 PETER MCLAUGHLIN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2003 LISA LESNY OUT TO CUSTOMER Completed