Permit Number: T03CM03872
Parcel: 123171690

Address:
1501 E MABEL ST

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM03872
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2003 EROSE1 WWM REVIEW Needs Review
11/10/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 1.0
1. Show access to the attic space. Ref. R807.

2. Remove the "no work to existing residence" note. The existing residence is having a wall demolished and shored to facilitate the construction of the addition.

3. Revise the site plan electrical note to read "feed wire to front of existing residence".

Sheet 3.0
1. Provide attic ventilation calculations and specify the size and location of venting. Ref. R806.

Sheet 4.0
1. Show the location of the rooftop mechanical equipment and account for the load in the truss design calculations. Ref. 802.10.1.

STRUCTURAL COMMENTS
General
1. Provide the engineered truss design, prepared and sealed by an Arizona P. E.

2. Coordinate with architectural comment 1, Sheet 4.0.

PLUMBING COMMENTS
Sheet 5.0
1. Specify that all tub/shower combinations will have control valves of the thermostatic or mixing valve type. Ref. UPC 410.7.

2. Provide a dimension for the horizontal drain line size from the clothes washer. Ref. UPC Table 7-5.

3. Remove the note specifying 3" waste from second floor.

MECHANICAL COMMENTS - The mechanical plan has been reviewed and approved.

ELECTRICAL COMMENTS
Sheet 6.0
1. Specify the circuit number for the weatherproof motion sensor.

2. Show the circuit numbers for the rooftop mechanical equipment and the rooftop receptacle. Specify a weatherproof ground fault circuit interrupter protected receptacle. Ref. E3802.3.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
11/10/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/10/2003 ELAINE ROSE OUT TO CUSTOMER Completed