Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03865
Parcel: 13331159T

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03865
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
08/05/2003 DAN CASTRO ZONING REVIEW Approved
08/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/06/2003 ROBERT SHERRY WATER REVIEW Approved
08/07/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide vent for new floor sink. Reference Section 901.0, UPC 1994.
2. Indicate how the vents will be terminated: connect to existing vents or extend above the roof? Reference Section 906.3, UPC 1994.
3. Include new floor sink in fixture list.
4. Increase the size of the font in the plumbing fixture list to a minimum of 10 points.
08/14/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/21/2003 JIM EGAN FIRE REVIEW Approved
08/22/2003 GERRY KOZIOL WWM REVIEW Approved
08/26/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide revised occupant load calculations. Reference section 1003.2.2 IBC.
2. Door # 4 is required to swing in direction of travel. Reference section 1003.3.1.2 IBC. Revise plans
3. Building has been classified per the UBC. Revise classification to the current adopted code, IBC.
4. Door to remain open during business hours may not be used. Reference section 1003.3.1.8 IBC. revise plans
5. Indicate on plan codes being used for design. Reference City of Tucson web page.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/28/2003 TAMI ACHONG OUT TO CUSTOMER Completed
08/26/2003 ANGIE SHOFFSTALL REJECT SHELF Completed