Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03865
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
08/05/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
08/06/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/06/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/07/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide vent for new floor sink. Reference Section 901.0, UPC 1994. 2. Indicate how the vents will be terminated: connect to existing vents or extend above the roof? Reference Section 906.3, UPC 1994. 3. Include new floor sink in fixture list. 4. Increase the size of the font in the plumbing fixture list to a minimum of 10 points. |
08/14/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/21/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
08/22/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/26/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide revised occupant load calculations. Reference section 1003.2.2 IBC. 2. Door # 4 is required to swing in direction of travel. Reference section 1003.3.1.2 IBC. Revise plans 3. Building has been classified per the UBC. Revise classification to the current adopted code, IBC. 4. Door to remain open during business hours may not be used. Reference section 1003.3.1.8 IBC. revise plans 5. Indicate on plan codes being used for design. Reference City of Tucson web page. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/28/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
08/26/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |