Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T03CM03821
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/21/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/03/2003 | TERRY STEVENS | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T03CM03821 9/03/03 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. GENERAL REQUIREMENTS: 1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312. 2. ALL FOUNDATION HOLD-DOWNS SHALL BE SPECIFIED AND LOCATED.---------SIMPSON DOES NOT MFG. A HPAHD42-------DO YOU MEAN A PAHD42? STRUCTURAL PLANS: 1. PROVIDE DETAIL OF NONBEARING WALL TO ROOF LEDGER. [RAFTERS PARALLEL TO WALL] 2. DETAIL 6/2 CALLED FOR AT ROOF FRAMING PLAN AND CROSS SECTIONS IS FOR A TOE DOWN NOT FRAMING. 3. DETAIL 2/2------PRESSURE TREATED SILL PLATE REQUIRED. 4. DETAIL POST TO BEAM CONNECTION AND CROSS REFERENCE TO FRAMING PLAN. ELEVATIONS: 1. NOTE AND SIZE ALL ROOF DRAINS OR SCUPPERS ON FLAT-ROOFED AREAS PER R903.4. PLUMBING PLANS: 1. WATER LINE: PROVIDE MAXIMUM DEVELOPED LENGTH. MECHANICAL PLANS: 1. 6" DUCT FOR COLD AIR RETURN IS NOT ADEQUATE. MODEL ENERGY CODE: 1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11. 2. CALL OUT ON THE PLANS THE "R" VALUES OF INSULATION, AS WELL AS THE "U" VALUES OF THE WINDOWS AND DOORS IN CONFORMANCE WITH THE ENERGY CALCULATIONS PROVIDED. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: TERRY STEVENS @ 791-5550 EXT. 1112 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/03/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |