Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03815
Parcel: 124081690

Address:
1321 E 10TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM03815
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2003 MELISSA POULIN WWM REVIEW Approved
09/02/2003 Christy Foreman BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM03815 / 9-5-2003
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.
SCOPE OF REVIEW:
THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.
GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.
SITE PLAN:
1. INDICATE THE LOCATION OF GAS, WATER AND SEWER OR ON THE PROPERTY, AND
WHERE THEY ENTER THE BUILDING.
FOUNDATION PLANS:
1. DIMENSION THE WALL THICKNESS, FOOTING WIDTH THICKNESS AND DEPTH INTO UNDISTURBED SOIL FOR EACH FOOTING TYPE AND CONDITION PER TABLE R403.1. SHOW SLAB IS 6" ABOVE FINISHED GRADE.

2. ALL SLABS AND PADS, INCLUDING LANDINGS AT ALL DOORS, SHALL BE SHOWN AND THEIR THICKNESS
SPECIFIED. INDICATE THE SLOPE FOR EXTERIOR SLABS, PER R312.

3. LOCATE AND SPECIFY ALL ANCHOR BOLT SPACING, EMBEDMENT 7" MIN. AND POST ANCHORS ON THE FOUNDATION PLAN.

4. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND
LOCATED.
FLOOR PLANS:
1. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

2. IDENTIFY CEILING HEIGHTS IN ALL AREAS ON FLOOR PLAN. IF SLOPED CEILING, NOTE AVERAGE HEIGHT.
ROOF PLAN:
1. NO PENETRATIONS ARE ALLOWED IN A 1 HR RATED WALL.

2. ROOF MAY NOT DRAIN ON A ADJACENT PROPERTY.
STRUCTURAL PLANS:
1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD
AND LIVE LOAD.

2. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:

· TRUSSES TO TOP PLATE - INDICATE YOUR BLOCKING OR RIM JOIST
· DETAIL ROOF RAFTERS TO NON-BEARING WALL


3. PROVIDE BRACING DETAILS AND NOTES FOR EXTERIOR FRAME WALLS AND MAIN CROSS-STUD PARTITIONS, OR USE FULLY BRACED, PER R602.10.3. A MINIMUM PANEL WIDTH OF 48" IS REQUIRED TO EFFECTIVELY BRACE THE PARTITION. SEE TABLE R602.10.3, CATEGORY "C". IF BRACING DOES NOT COMPLY, PROVIDE A LATERAL ANALYSIS OR ALTERNATE DESIGN TO BE REVIEWED BY THE PLANS EXAMINER. WIND FORCES FOR SINGLE STORY RESIDENCES SHALL USE 90 MPH, EXPOSURE "B". TWO STORY RESIDENCES OR AREAS OF HIGHER WIND SHALL USE EXPOSURE "C".

SECTIONS - DETAILS - MISC. NOTES:
1. NOTE AND SPECIFY THE SIZE, SPACING AND LENGTH OF ANCHOR BOLTS FOR SILL PLATES, TOP PLATES AND
LEDGERS. EMBEDMENT FOR ANCHORS A MIN. OF 7".
PLUMBING PLANS:
1. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH
MECHANICAL PLANS:
1. INDICATE SIZE OF RETURN AND SUPPLY DUCTS.
ELECTRICAL PLANS:
1. PROVIDE AN EXTERIOR OUTLET AT GRADE LEVEL LOCATED AT BOTH THE FRONT AND BACK OF THE DWELLING, PER E3801.7. THESE OUTLETS SHALL BE GFI PROTECTED PER E3802.3.

2. ISLAND OR PENINSULA COUNTER TOPS SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET AT EACH
COUNTER SPACE WITH A LONG DIMENSION OF 24" OR GREATER, AND A SHORT DIMENSION OF 12" OR
GREATER, PER E3801.4.2 AND E3802.4.3.

3. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS

4. INDICATE GFI ON ROOF AND SHOW A/C TAKING CIRCUIT 1 & 3.

5. #6 WIRE INADEQUATE FOR ESTIMATED EXISTING 125 AMP LOAD @ SUB-PANEL.

6. SPECIFY WIRE SIZE AT PANEL SCHEDULE.

7. BREAKERS NOT INDICATED FOR SUB-PANEL ON MAIN SERVICE.

MODEL ENERGY CODE:

1. PROVIDE 2 COPIES OF ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.
IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
CHRISTY FOREMAN @ 791-5550 EXT. 1113

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
09/05/2003 CINDY AGUILAR REJECT SHELF Completed