Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
08/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM03808

Denied 080103 for lack of panel schedules and load calculations.

DENIED A SECOND TIME 081203 FOR REASONS BELOW:
1- Per NEC 230-2, a building or other structure served shall be supplied by only one service. However, see Article 100, Definitions for "Building". If a fire wall separates the tenant area for panel "C" and its associated new service, then the concept is acceptable. Plans do not document such fire wall.
08/13/2003 MVALDEZ1 FIRE REVIEW Needs Review
08/13/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/13/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
08/13/2003 MONICA VALDEZ APPROVAL SHELF Completed