| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM03808 Denied 080103 for lack of panel schedules and load calculations. DENIED A SECOND TIME 081203 FOR REASONS BELOW: 1- Per NEC 230-2, a building or other structure served shall be supplied by only one service. However, see Article 100, Definitions for "Building". If a fire wall separates the tenant area for panel "C" and its associated new service, then the concept is acceptable. Plans do not document such fire wall. |
| 08/13/2003 | MVALDEZ1 | FIRE | REVIEW | Needs Review | |
| 08/13/2003 | GERRY KOZIOL | WWM | REVIEW | Approved |