Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03807
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/01/2003 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
08/01/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Location of floor sink P-5 does not conform to the requirements of Section 804.1, UPC 1994. |
08/01/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/01/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/01/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
08/01/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the consruction space above the ceiling is suitable for use as a return air plenum. Reference Section 602.2.1, IMC 2000. |
08/04/2003 | PETER MCLAUGHLIN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/12/2003 | TACHONG1 | WWM | REVIEW | Needs Review | |
08/12/2003 | TACHONG1 | FIRE | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/12/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |