Permit Number: T03CM03799
Parcel: 117042400

Address:
529 N 6TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03799
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2003 JIM EGAN FIRE REVIEW Approved
08/04/2003 JIM TATE ENGINEERING REVIEW Denied Site Plan approval is required prior to building plan approval.
08/05/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete plumbing plan, including waste and vent isometrics. Reference Section 302.3, Uniform Administrative Code 1997.
2. Provide more detailed fixture descriptions and listing information for all plumbing fixtures (e.g. Is the water closet equipped with a flush valve or a tank? Does the water closet comply with Section 401.1, UPC 1994?).
3. The maximum flow rates for plumbing fixtures shall be consistent with ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.state.az.us/ArizonaRevisedStatutes.asp) Reference Section 402.1, UPC 1994, as amended by the State of Arizona.
4. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 1994 with AZ State amendments.
5. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994.
6. Provide location and size of RPBP assembly.
7. Provide rim elevation of next upstream sanitary manhole and first floor elevation. Determine need for backwater valve per Section 710.1, UPC 1994.
8. Provide vent piping of sufficient size to comply with Section 904.1, UPC 1994.
9. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Section 704.4, IECC 1998.
08/05/2003 ROBERT SHERRY WATER REVIEW Approved
08/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The submitted energy calculations are not consistent with the building plans.
a. The town of Pima, AZ is in climate zone 6b; Tucson, AZ is in climate zone 4b.
b. According to the building drawings, the exterior walls are double wythe brick without furring, not unfurred 8" CMU as shown on the energy calculations.
2. Provide design heating and cooling load calculations to verify the size of the HVAC equipment. Reference Section 703.2.1, IECC 1998.
08/13/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. An accessible route is required to the public way unless technically unfeasible. Reference section 3408.3 IBC. Please clarify
2. Doors # 105, 001, and 007 do not meet the maneuvering clearances per section 404.2.4 ANSI A117.1. Revise plans.
3. Show how ventilation for attic and crawl spaces are to be obtained. Reference section 1202 IBC.
4. Provide access to attic and under floor areas per section 1208 IBC
08/20/2003 GERRY KOZIOL WWM REVIEW Approved
08/25/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
8/25/2003
Copies of the stamped approved site and landscape plans must be included in the submittal package prior to review and approval.
08/27/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Water heater not to be cord connected. 2. Indicate conduit and conductor sizes @HP-1 (indoor unit). 3. HP-1(outdoor) & HP-1 appear to be crossed or improperly identified at panel schedule. 4.Water heater is required to have a disconnect at the W.H. location.5. Properly calculate cir. A-4(see N.E.C. for calculating track lighting loads). 6.Provide wattage,lamp type,fixture description etc. for fixture " I ". 7. Describe light pole. 8. Provide pole base detail. 8. Provide the wattage for the emergency/exit lighting.
5.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2003 TAMI ACHONG OUT TO CUSTOMER Completed
08/28/2003 ANGIE SHOFFSTALL REJECT SHELF Completed