Permit Number: T03CM03775
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM03775
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the existing fixtures in the pipe sizing calculations.
2. The pedicures are noted as having 1/2" CW and HW connections - according to Table 6-3, 4 the correct number of fixture units is 4 per pedicure.
3. Include the pressure drop for the water meter in the calculations.
4. Limit the velocity of the water to 8 fps in copper pipe.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2003 SUE REEVES OUT TO CUSTOMER Completed