Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03775
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include the existing fixtures in the pipe sizing calculations. 2. The pedicures are noted as having 1/2" CW and HW connections - according to Table 6-3, 4 the correct number of fixture units is 4 per pedicure. 3. Include the pressure drop for the water meter in the calculations. 4. Limit the velocity of the water to 8 fps in copper pipe. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/19/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |