| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include the existing fixtures in the pipe sizing calculations. 2. The pedicures are noted as having 1/2" CW and HW connections - according to Table 6-3, 4 the correct number of fixture units is 4 per pedicure. 3. Include the pressure drop for the water meter in the calculations. 4. Limit the velocity of the water to 8 fps in copper pipe. |