Permit Number: T03CM03775
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03775
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2003 JIM TATE ENGINEERING REVIEW Approved
07/30/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
07/31/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Cordinate location of water heater with architecural floor plan, A2.
2. Provide water pressure and pipe sizing calculations. Include existing fixtures in the calculations.
3. Provide drain for RPBP-1.
4. Provide access and maintenence platform for RPBP-1.
5. If pedicure stations do not have an integral air gap or listed backflow device, a reduced pressure backflow preventer will be required for both hot and cold water supplies.
07/31/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
07/31/2003 ROBERT SHERRY WATER REVIEW Approved
07/31/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/05/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Denied 8/5/03.
08/19/2003 SREEVES1 WWM REVIEW Needs Review
08/19/2003 SREEVES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2003 SUE REEVES OUT TO CUSTOMER Completed