Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM03775
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 07/30/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/31/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Cordinate location of water heater with architecural floor plan, A2. 2. Provide water pressure and pipe sizing calculations. Include existing fixtures in the calculations. 3. Provide drain for RPBP-1. 4. Provide access and maintenence platform for RPBP-1. 5. If pedicure stations do not have an integral air gap or listed backflow device, a reduced pressure backflow preventer will be required for both hot and cold water supplies. |
| 07/31/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/31/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/31/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/05/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Denied 8/5/03. |
| 08/19/2003 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 08/19/2003 | SREEVES1 | FIRE | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |