Permit Number: T03CM03773
Parcel: 10602265B

Address:
320 W PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM03773
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2003 JIM EGAN FIRE REVIEW Denied PROVIDE COMPLETE CODE REVIEW CHECKLIST.
09/26/2003 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. At any point where a ten (10) year flood discharge starts to cross a sidewalk or a pedestrian access, the sidewalk/access shall be designed and constructed to convey the ten (10) year flood flows under the sidewalk/access. Splashguards are not acceptable on sidewalks therefore downspouts are required and need to convey discharge under the sidewalk. Indicate dimensioned details of downspouts and splashguards. D.S. 2-08.5.1.E

2. The proposed signage is located in the existing and future sight visibility triangles which not acceptable. Correct and revise sign to be outside the SVT's. D.S. 2-02.2.1.A.13

3. Curbs are not acceptable for refuse enclosures. Indicate a dimensioned refuse enclosure detail as per D.S. 6-01.4.0 thru D.S. 6-01.4.2 and D.S. 6-01.10.Figure 2
10/14/2003 DAN CASTRO HANDICAP-SITE REVIEW Denied Refer to zoning review comment number one (1).
10/14/2003 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Detail disabled access aisle and ramp or indicate by note that access aisle is flush with pavement and sidewalk. (D.S. 2-02.2.1.A.8)

2. Correct the recording page for the ingress/egress easement from 955 to 995. (D.S. 2-02.2.1.A.11)

3. The proposed sign will be required to be removed by the owner at time of road widening at no expense to the City. (D.S. 2-02.2.1.A.13, .25)

4. A copy of the recorded Major Streets and Routes Covenant was not found in the submittal package. Please provide a copy to the Zoning Review Section for DSAD records.

5. This plan may be reviewed over the counter by the Zoning Review Section. Please contact Dan Castro to set an appointment.

6. All requested changes must be made to the site and landscape plans.


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
10/20/2003 JOE LINVILLE NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2003 TAMI ACHONG OUT TO CUSTOMER Completed