Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03770
Parcel: 12104107B

Address:
5704 E GRANT RD

Review Status: Completed

Review Details: REVISION

Permit Number - T03CM03770
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete plumbing plans, sealed by an Arizona registrant.
2. Show how the temperature and pressure reliefs for the relocated water heaters will be routed and terminated. Reference Section 608.5, UPC 1994.
3. Show how the pvc condensate drains are to be protected from exposure to sunlight. Reference Section 313.3, IAPMO IS 9-92.
10/20/2003 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2003 CINDY AGUILAR APPROVAL SHELF Completed
10/20/2003 CINDY AGUILAR OUT TO CUSTOMER Completed