Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03764
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 08/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/25/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | denied 8/5/03 |
| 08/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanouts for waste line from darkroom sinks. Reference Section 707.1, UPC 1994. 2. Provide cleanout for horizontal waste from floor sink. Reference Section 707.1, UPC 1994. 3. Darkroom sinks are to be directly connected to the building drain; the sinks do not meet the requirements of Section 801.2, UPC 1994 to be indirectly wasted. |
| 08/26/2003 | CAGUILA1 | WWM | REVIEW | Needs Review |