Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/30/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide water pressure and fixture unit calculations. Include existing fixtures in the calculations.
2. Show existing water, waste, and drain piping on plans.
3. Provide water and waste riser diagrams of new installations.
4. Provide calculations for sizing of the condensate drains.
5. Show termination of condensate drains.
07/30/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate Mechanical HVAC Plan with Mechanical Roof Plan.
2. Coordinate supply air volumes shown on the Mechanical Floor Plan with the Outside Air Compliance table.
3. Complete the rooftop unit schedule to include the rated gas input.
07/30/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/30/2003 ROBERT SHERRY WATER REVIEW Approved
07/30/2003 JIM EGAN FIRE REVIEW Approved
08/05/2003 TACHONG1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/05/2003 TACHONG1 WWM REVIEW Needs Review
08/05/2003 TACHONG1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2003 TAMI ACHONG OUT TO CUSTOMER Completed