Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03753
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/05/2004 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire hydrants required. Submit approved COT Water Plan. 2. Provide complete fire sprinkler system design criteria on plans. 3. Riser detail (Sht. FP1.1) is incorrect. |
01/05/2004 | GERRY KOZIOL | WWM | REVIEW | Denied | DEQ - See comment letter (copy attached to plans) |
12/22/2003 | Loren Makus | ENGINEERING | REVIEW | Denied | The site plan/building plan cannot be approved until the development plan has been approved. |
12/24/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 12/24/2003 Building plans may not be reviewed and approved until copies of the approved development and landscape plans are included in each set of the building drawings. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/12/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
02/10/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |