Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03CM03753
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/15/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
09/15/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | |
09/17/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire hydrants required. Submit approved COT Water Plan. 2. Provide complete fire sprinkler system design criteria: a. Design standard to be used. b. Hazard Classification. c. Minimum design density and area of application. d. Water Supply Information.___ Static psi ___Residual psi ___ Flow GPM. 3. Riser detail on sheet FP1.1 is incorrect. |
09/19/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Development Plan must be approved before building plans may be approved. |
09/19/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/23/2003 | MELISSA POULIN | WWM | REVIEW | Denied | Need WW/IWC review of photo operation - Tom Tomchak 579-5771 Need to build public sewer |
10/01/2003 | Patricia Gehlen | ZONING | REVIEW | Denied | Zoning 10/1/2003 Copies of the approved development, landscape and NPPO plans must be included in each set of the building plans prior to review and approval. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/30/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
10/01/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |