Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03753
Parcel: 13610023L

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM03753
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
09/15/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
09/17/2003 JIM EGAN FIRE REVIEW Denied 1. Fire hydrants required. Submit approved COT Water Plan.
2. Provide complete fire sprinkler system design criteria:
a. Design standard to be used.
b. Hazard Classification.
c. Minimum design density and area of application.
d. Water Supply Information.___ Static psi ___Residual psi ___ Flow GPM.
3. Riser detail on sheet FP1.1 is incorrect.
09/19/2003 LOREN MAKUS ENGINEERING REVIEW Denied Development Plan must be approved before building plans may be approved.
09/19/2003 ROBERT SHERRY WATER REVIEW Approved
09/23/2003 MELISSA POULIN WWM REVIEW Denied Need WW/IWC review of photo operation - Tom Tomchak 579-5771
Need to build public sewer
10/01/2003 Patricia Gehlen ZONING REVIEW Denied Zoning
10/1/2003
Copies of the approved development, landscape and NPPO plans must be included in each set of the building plans prior to review and approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/30/2003 TAMI ACHONG OUT TO CUSTOMER Completed
10/01/2003 ANGIE SHOFFSTALL REJECT SHELF Completed