Review Details: COMMERCIAL TI

Permit Number - T03CM03713
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/30/2003 ROBERT SHERRY WATER REVIEW Approved
07/30/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide cleanout for water closet P-1. Reference Section 707.4, UPC 1994.
2. A service sink is not an approved termination point for the T&P relief. Reference Section 608.5, UPC 1994.
3. Provide access to the water heater per Section511.2, UPC 1994.
4. Provide water pressure and pipe sizing calculations.
07/30/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations based on Sections 403.3 and 403.3.2, IMC 2000.
2. Provide energy code compliance calculations.
07/31/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2003 TACHONG1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2003 TAMI ACHONG OUT TO CUSTOMER Completed