Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM03695
Parcel: 121063820

Review Status: Completed

Review Details: RESIDENTIAL W/ COMM BLDG/ZONING/ENGINE

Permit Number - T03CM03695
Review Name: RESIDENTIAL W/ COMM BLDG/ZONING/ENGINE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS



1) Provide erection details and procedures to erect.
2) Specify the type of connectors at the seam connecting each panel.
3) Are all connectors the same? If different specify. Specify any special conditions.
4) Engineer of record to approve the 2 openings shown on the south elevation of
Separate sheet.
11/20/03

5) A 1-Hr wall is required on the west side of structure or move building 4' more
To the east, making it a total of 10' from the west property line.
11/29/2003 Terry Stevens BUILDING-RESIDENTIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2003 LISA LESNY OUT TO CUSTOMER Completed
12/02/2003 LISA LESNY APPROVAL SHELF Completed