Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM03666
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM03666
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied 1. On Electrical Plan, correct the designation "SWGR 20" to SWGR 21" such that they agree with the Panel Schedule.
2. Specify which branch circuits relocated from Panel 2 are to go to which circtuis on Panel SWGR, such as Sprinklers from Ckt 3, Concessions Outlet from 5,7, Snack Bar from 9, and Snack Bar from 10,12.
3. Provide load calculations for Panel SWGR.
4. Please note that this is City work. Specifications refer in several places to "Pima County Parks and Recreation Department" in several places. See, for example, 16510 and 16990.
08/08/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T03CM03666 .. 3700 S MISSION RD .. DGL .. 8/8/03 .. .. .. S1. DIMENSIONALLY LOCATE LIGHT POLES FROM TWO ADJACENT PROPERTY LINES. ....................................... .. S2. SUBMIT TWO SETS OF APPROVED SHOP DRAWING FOR LIGHT POLES INCLUDING ANCHOR BOLTS, AS NOTED. .................................................................... .. S3. SPECIAL INSPECTION REQUIRED AS NOTED FOR : ........ 1. CAISSONS ........................................................ ........ 2. CONCRETE ....................................................... ........ 3. REINFORCEMENT ............................................. ........ 4. LIGHT POLES .................................................... ........ 5. ANCHOR BOLTS .

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
08/11/2003 ANGIE SHOFFSTALL REJECT SHELF Completed