Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03CM03657
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/13/2004 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Approved | |
| 05/13/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/13/2004 | JIM EGAN | FIRE | REVIEW | Approved | 1. Provide complete code review checklist for new and existing buildings. Indicate type of construction, area, fire rating of exterior walls and opening protection for new building and existing buildings located north and south of new building. 2. Provide floor plan for existing basement. Indicate occupancy/use and existing exits. 3. Fire sprinklers required for existing basement. 4. Provide complete fire sprinler design criteria, on plan, to include existing basement. |
| 05/13/2004 | GP | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | |
| 05/14/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 05/14/2004 | DAN CASTRO | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/25/2004 | ANGIE SHOFFSTALL | APPROVAL SHELF | Completed |
| 05/14/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |