Permit Number: T03CM03657
Parcel: Unknown

Address:
222 S FREEWAY M1

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM03657
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2004 EROSE1 WWM REVIEW Needs Review
02/11/2004 EROSE1 ENGINEERING REVIEW Needs Review
02/11/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied STRUCTURAL COMMENTS
General
1. Please specify all Special Inspection items on plan. Reference IBC 1704 and address excavations, masonry and field welding.

2. Update call out references on Sheet E-08 for consistency with details provided on Sheet E-09.

3. Clarify responsibility for lateral and gravity design of two platforms between Lines 1 and 1a. Steel manufacturer's calculations do not appear to account for such loads. See Framing Plan shown on Sheet 4 or Steel Manufacturer Sheet E-08 and complete structural design, brace specification and detailing.

4. Reference Details 8, 9, 10, and 11 on Sheet 6 and clarify attachment of masonry blocks to steel frames at decorative walls. Also address whether these walls are connected to the building structure.

5. Recheck seismic parameters and seismic base shear calculations prepared by Jesus Florez, which appear to be in conflict with Steel Manufacturer Design Data. Verify that Soil Site Class "C" can be used if Soils Report for the proposed site is provided. Otherwise Soil Site Class "D" shall be used per IBC 1615.1.1, last paragraph. Ref. IBC 1615 and update.

6. Coordinate with Final Steel Frame Calculations and provide foundation design for steel frame columns with footings which are different from previous submittal package. The Engineer of Record shall provide foundation design due to compression, shear and uplift and anchor bolt connection at foundation base plate. Please complete. Clarify missing footing details and pedestals below steel columns.

7. Similarly complete footing specification at interior columns along Line 1.
02/11/2004 ELAINE ROSE ZONING REVIEW Needs Review
02/11/2004 EROSE1 WATER REVIEW Needs Review
02/11/2004 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2004 ELAINE ROSE OUT TO CUSTOMER Completed