Permit Number: T03CM03572
Parcel: 110055420

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03572
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2003 JIM EGAN FIRE REVIEW Approved
07/21/2003 DAN CASTRO ZONING REVIEW Approved
07/21/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/22/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the difference between P-6 in the Nurse's room and P-6 in the break room. A 2-compartment sink will have 3 waste fixture units and 4 water fixture units.
2. A service sink with a 3" trap (P-4) has 6 waste fixture units.
3. Coordinate the riser diagram (detail 4/P1) with the floor plans.
4. Include all of the fixtures in the fixture unit calculations (e.g. existing hose bibb).
5. Coordinate the riser diagram in detail 2/P1 with the floor plans.
6. Based on your calculations, the CW pipe at keynote 2, and the CW and HW pipes downstream of the WH-1 connection are undersized.
7. The mop sink, P-4, is not an approved termination point for the excess pressure relief for the water heater.
07/22/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/22/2003 ROBERT SHERRY WATER REVIEW Approved
07/22/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved 072203 denied
07/22/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation calculations conforming to able 403-3, IMC 2000. Exception to Section 403.3 can apply only if a statistical study of the conditions is presented. Indicate the occupancy classification and estimatyed maximum occupancy used for each space on your calculation table.
2. Provide ventilation for the janitor's room (Utility Space).
3. Indicate which a/c units are serving specific areas on the Chapter 4 compliance chart.
07/23/2003 MELISSA POULIN WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/23/2003 MONICA VALDEZ REJECT SHELF Completed
07/23/2003 MONICA VALDEZ OUT TO CUSTOMER Completed