Permit Number: T03CM03562
Parcel: 12405023A

Address:
811 N EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03562
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2003 JIM EGAN FIRE REVIEW Approved
07/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Vents from indirect wastes may not connect to sewer-connected vents. Reference Section 803.0, UPC 1994.
2. A floor sink cannot be connected to a grease trap. Reference Section 1011.3, UPC 1994.
3. The drawing shows a grease trap, not a grease intercepter. Please confirm.
4. Confirm the C.A. tank contains compressed air; compressed air is not the same as carbon dioxide.
5. Provide pipe sizing calculations and sizes of existing water pipes.
6. Provide verification of BTU content of natural gas used in calculations.
07/21/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
07/21/2003 ROBERT SHERRY WATER REVIEW Approved
07/21/2003 DAN CASTRO ZONING REVIEW Approved
07/21/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Provide balancing information for kitchen hoods (both exhaust and make-up air) being reused.
07/21/2003 PATRICIA GILBERT ENGINEERING REVIEW Approved
07/22/2003 MVALDEZ1 WWM REVIEW Needs Review
07/22/2003 MVALDEZ1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2003 MONICA VALDEZ OUT TO CUSTOMER Completed