01/03/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ELECTRICAL COMMENTS
Sheet E2
1. Equipment item 34 was not found in the panel schedule. It appears that this is to be served by circuit "B-5". Please clarify.

2. Equipment items 1 and 2 did not include amps in the schedule and were not found on the power plan. Please provide this information.

Sheet E3
1. Circuits A-2 and A-4 for the 40 amp fan coil and heat strip are specified in panel A to utilize #10 THWN. Allowable ampacities for this type of conductor suggest that #8 THWN is required. Ref. NEC Table 310-16.

2. Circuit B-14 is described as equip-20 & 28. It appears this should be equip-20 & 18. Please clarify.

ENERGY COMMENTS - The energy portion has been reviewed and approved.