Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM03551
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/03/2004 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ELECTRICAL COMMENTS Sheet E2 1. Equipment item 34 was not found in the panel schedule. It appears that this is to be served by circuit "B-5". Please clarify. 2. Equipment items 1 and 2 did not include amps in the schedule and were not found on the power plan. Please provide this information. Sheet E3 1. Circuits A-2 and A-4 for the 40 amp fan coil and heat strip are specified in panel A to utilize #10 THWN. Allowable ampacities for this type of conductor suggest that #8 THWN is required. Ref. NEC Table 310-16. 2. Circuit B-14 is described as equip-20 & 28. It appears this should be equip-20 & 18. Please clarify. ENERGY COMMENTS - The energy portion has been reviewed and approved. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/03/2004 | ELAINE ROSE | OUT TO CUSTOMER | Completed |