Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM03513
Parcel: 13613027F

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM03513
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide a complete allowable area calculation including existing buildings. Reference section 503 IBC
2. Plans do not indicate number and location of required plumbing facilities. Reference Chapter 29 IBC. Provide plumbing fixture calculations and location per table 2902.1 and section 2902.3 IBC
3. Provide door hardware schedule for all exit doors. Reference chapter 10 IBC
4. Occupant load exceeds 300. An automatic sprinkler system is required. Reference section 903.2.1.3 IBC. Revise plans
5. How is accessibility to be achieved? Reference section 3408.4 IBC
6. Floor plan (sheet 3) differs from electrical plan. Please clarify
7. Assembly area may not exit threw a kitchen. Provide exit travel and width calculations. Reference section1004.2.3 IB
8. Floor plan notes (sheet 7) reference residential applications and conflict with structural sheets. Revise Plans
9. Revise notes on sheet 5 to reflect engineering calculations.
10. Remove references to the IRC on sheet 5.
11. How are accessible routes and entrances being achieved? Reference section 1108 IBC
08/21/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation for addition. Reference Section 403, IMC 2000.
2. Provide energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1997.
08/22/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Provide IECC calculations for Lighting Power Budget.
2. Provide Lighting Fixture cut sheets and schedule. This is a submittal requirement, and is necessary to determine proper electrical requirements of such fixtures and to evaluate compliance with the Lighting Ordinance.
3. Circuit 27 should have 9 amps not 6. Per NEC 220-3 (B) (9), receptacle outlets shall be computed at no less than 180 VA (duplex). (180) (6) = 1080/120 = 9.
4. For the new SD on CKT 25, fill this in on the Panel Schedule.
5. Show the panel/service location in plan view.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
08/22/2003 ANGIE SHOFFSTALL REJECT SHELF Completed