Permit Number: T03CM03500
Parcel: 12511199B

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM03500
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/15/2003 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Correct and revise Project Site location on Location map.

2. Indicate parcel tax code along with lot description.

3. A 5 foot sidewalk from street to buildings is required and it cannot cross behind parking spaces. D.S. 2-02.2.1.A.12. Sidewalks shall be designed and constructed to convey the 10 year flood flow under the sidewalk. D.S. 3-01.4.4.F

4. Indicate if street is "Public" or "Private". D.S. 2-02.2.1.A.18

5. Indicate dimension from street monument lines to all existing and proposed curbs, sidewalks, driveways and utility lines. D.S. 2-02.2.1.A.21

6. P.A.A.L. indicates to be 22 feet in width. The minimum width for two (2) way traffic aisles is twenty-four (24) feet. D.S.3-05.2.1.C.1 and D.S. 3-05.2.2.B.1-4 Correct and revise.

7. Indicate dimensions for driveway apron.

8. Indicate existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number. D.S. 2-02.2.1.A.23

9. New projects including mobile home parks consisting of three (3) or more dwelling units will provide centralized on-site refuse storage, collection, and pickup areas with service access from within the tract or from an alley adjacent to the tract. For approval of proposed design, contact John Clark or Environment Services at 791-3175 ext.1136. D.S. 6-01.2.2

10. A Grading Permit is required. Fill quantities equal 184 c.y.
12/16/2003 ASHOFFS1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed