Permit Number: T03CM03500
Parcel: 12511199B

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM03500
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2003 BLANCA ESPINO ENGINEERING REVIEW Denied Approved site plan required.
09/26/2003 ELAINE ROSE ZONING REVIEW Needs Review
09/26/2003 EROSE1 WWM REVIEW Needs Review
09/26/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. The City of Tucson requires apartment projects to be designed and sealed by an architect registered in the State of Arizona

2. Provide the site plan for this project.

Sheet 2
1. Remove references to the Uniform Building Code and International Residential Code.

STRUCTURAL COMMENTS
General
1. Please provide the lateral load analysis and calculations for the project.


Sheet 2
1. Provide the calculations and design for the retaining walls.

2. Account for concentrated loads of rooftop equipment. Ref. IBC 1606.2.

PLUMBING COMMENTS
Sheet 8
1. Provide the site plumbing plan. Include fixture unit schedules and supply calculations.

MECHANICAL COMMENTS
Sheet 7
1. The mechanical, plumbing and electrical plans show different types of equipment. Please coordinate and clarify.

ELECTRICAL COMMENTS
General
1. Provide the site electrical plan.

Sheet 6
1. Provide the one line diagram, load calculations and fault current provisions.

ENERGY COMMENTS
General
1. Provide energy code compliance data. Ref. IECC.
09/26/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2003 ELAINE ROSE OUT TO CUSTOMER Completed