Permit Number: T03CM03475
Parcel: 12710229A

Address:
603 N WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM03475
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/21/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Approved
08/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Some of the hot and cold water piping is undersized when compared to the calculations shown on sheet CP-5.1. Confirm calculations and resize the pipes. Reference Section 302.3, Uniform Administrative Code 1997.
2. The wall box for the standpipe accepting the temperature and pressure relief from the water heater must be listed for relief service use.
09/02/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/10/2003 MELISSA POULIN WWM REVIEW Denied Plan needs to go to 8th floor for evaluation of Walt Valencia's comment regarding drain.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/11/2003 LISA LESNY OUT TO CUSTOMER Completed
09/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed