Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM03475
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/21/2003 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/21/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Some of the hot and cold water piping is undersized when compared to the calculations shown on sheet CP-5.1. Confirm calculations and resize the pipes. Reference Section 302.3, Uniform Administrative Code 1997. 2. The wall box for the standpipe accepting the temperature and pressure relief from the water heater must be listed for relief service use. |
09/02/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/10/2003 | MELISSA POULIN | WWM | REVIEW | Denied | Plan needs to go to 8th floor for evaluation of Walt Valencia's comment regarding drain. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/11/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
09/10/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |