Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM03475
Parcel: 12710229A

Address:
603 N WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM03475
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
07/14/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
07/15/2003 JIM EGAN FIRE REVIEW Approved
07/16/2003 GERRY KOZIOL WWM REVIEW Denied Cannot drain 2" water wall basin to sewer.
07/18/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Termination of the excess pressure relief from the water heater over a mop sink is not approved location. Reference Section 608.5, UPC 1994.
2. Add missing pipe sizes to Detail 4/CP-4.1, coordinate with pipe sizes shown on floor plans, and change the title of the detail to match subject. Reference Section 302.3, Uniform Administrative Code 1997.
3. Resize wet vents shown in Detail 3/CP-4.1 to comply with the requirements of Section 908.2, UPC 1994, and change the title of the detail to match subject.
4. Resize wet vents shown in Detail 1/CP-4.1 to comply with the requirements of Section 908.2, UPC 1994.
5. Provide cleanouts for the waste piping for the second floor to comply with Section 707.4, UPC 1994, as amended by the State of Arizona.
6. Show the route of the cold water supply to aquarium located on the second floor. Reference Section 302.3, Uniform Administrative Code 1997.
7. Show all pipe sizes on detail 2/CP-4.1; coordinate with pipe sizes shown on floor plans. Reference Section 302.3, Uniform Administrative Code 1997.
8. Most of the hot and cold water piping is undersized when compared to the calculations shown on sheet CP-5.1. Confirm calculations and resize the pipes. Reference Section 302.3, Uniform Administrative Code 1997.
9. Coordinate pipe sizes shown on details 1/CP-5.1, 2/CP-4.1, and sheet CP-3.1. Reference Section 302.3, Uniform Administrative Code 1997.
10. Include the water supplies to the humidifiers, fountain, and aquarium in the fixture unit calculations. Reference Section 302.3, Uniform Administrative Code 1997.
07/18/2003 ROBERT SHERRY WATER REVIEW Approved
07/18/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Provide energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1997.
3. Provide minimum efficiency requirements for packaged and split system data air conditioning units. Reference Section 703.3, IECC 1998.
4. Provide information to show that the air conditioning systems for rooms 006 and 015 conform to the requirements of Section 1102, IMC 2000.
5. Provide auxiliary drain pans or secondary drain systems for fan coil unit, HFC-1. Reference Section 307.2.3 IMC.
6. Materials exposed in plenums shall conform to Section 602.2.1, IMC.
7. Coordinate drawings CM-2.0 and CM-2.1; one 14"x6" outside air duct shown on CM-2.0 and two 14"x6" outside air ducts shown on CM-2.1. Reference Section 302.3, Uniform Administrative Code 1997.
8. Provide supply and exhaust airflow rates for rooms 277 and 278. Reference Section 302.3, Uniform Administrative Code 1997.
9. Complete schedule information for Packaged Data Air Conditioning units. Provide details to show how the unit will be applied to avoid rejecting heat to the interior of the building. Reference Section 302.3, Uniform Administrative Code 1997.
08/01/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/12/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Show how the folding partition is being supported. Engineering calc`s might be
required.
2) Provide safety glazing as per section 2406 of the IBC. Note on plans.
3) Show how ladder is attached at roof hatch. Provide a connection detail.
4) Show location of fire extinquisher.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2003 TAMI ACHONG OUT TO CUSTOMER Completed
08/12/2003 ANGIE SHOFFSTALL REJECT SHELF Completed